Cyclades PM42 3-Phase
Intelligent Power Distribution Unit
Cyclades® PM42 3-phase intelligent power distribution unit (IPDU) enables remote power control and system management of IT assets located within data centers that utilize or plan to use more than 5kW of power within server racks. When used in conjunction with Cyclades ACS advanced console servers and DSR® switches, the Cyclades PM 42 IPDU offers quick problem resolution through an integrated management interface. With one or more outlets positively associated with a particular device, users may control power “in line†through a user-defined “hot key†or by using an intuitive Web browser-based GUI.
The unit includes two RS 232 ports: one for remote management through Cyclades ACS console servers, DSR switches as well as DSView® 3 management software, and the second one for daisy chain expansion. Daisy chaining allows operators to control up to 3 units as a single device. Remote management capabilities include event logging and fault notification via email, SMS or SNMP traps.
Cyclades PM42 is equipped with 42 IEC320-C13 power outlets and a fixed power cable with L21-30 termination. It accepts 208Vac 3-phase input voltage and converts this to three separate banks of split-phase 208Vac circuits suitable for powering IT equipment.
Cyclades PM42 Quick Facts
Power control over remote IT assets from anywhere on Earth
Support high density racks
Seamless integration with Cyclades ACS console servers, DSR switches and DSView 3 software
Monitor and balance current to optimize power delivery
Proactive fault management and isolation
Fault notifications via email, SMS page and SNMP traps
Features and Benefits
Feature
Benefit
3-phase input power
Reduce the number of power distribution units required to provide higher power requirements to a single rack
Consolidated interface for IT assets as well as power management that provides multiple ways to manage Telnet, SSH, SNMP or secure Web session as well as grouping capabilities for outlets
Individual outlet control
Saves downtime associated with hung up servers and network gear
Phase level metering
Simplifies moves, add-ons and changes while monitoring power consumption costs
Electronic overcurrent protection
Avoids nuisance trips by locking unused outlets when programmable thresholds are exceeded
Sequential start up
Ensures breakers do not trip due to high inrush currents
Flexible mounting options
Several mounting holes provide installation flexibility
Outlet retention clips
Prevents accidental unplugging of loads
Daisy-chaining capability
Conservation of valuable console and switched ports
Built-in temperature sensor
Provides integrity of equipment as soon as racks surpass temperature thresholds
UL60950-1 compliant
Ensures safety
Specifications
Mechanical
Height
72 in. (182.9 cm)
Width
2.2 in. (5.6 cm)
Depth
2.5 in. (6.3 cm)
Weight
24 lbs. (10.9 kgs.)
Interfaces
1 RS-232 serial port (9,600 8-N-1)
42 IEC 320-C13 outlets
Multi-daisy chaining capability up to three units
Environmental
Operating Temp
0ºC to 50ºC
Storage Temp
–20ºC to 70ºC
Humidity
Operating
20% to 80% noncondensing
Storage
5% to 95% noncondensing
Power
Input power
3-ph 208V nominal, 50/60Hz
Maximum input current: 24A
Maximum output power (entire strip): 8.7kVA
Maximum output current per phase: 16A
Maximum output current per outlet: 10A
Cabling
Computers
Fixed 15’ input power cable terminated with
NEMA L21-30P plug
Output: 42 IEC 320-C13
Certifications
EMC/Interference: FCC part 15
Safety: CSA (fully compliant with UL standard)